| INPUTS: | - 4 ANALOG 3870 points | NTC -50°C...+115°C (SX) |
| - 12 conversions/sec | PT100/PT1000 (2 wire) Thermocouple J-K-N-R-S-T | |
| - digital filtering | 0-5V / 4-20mA | |
| - thermal drift typ. 1 point. | Potentiometer / Switch / Commutator | |
| WX (anemometer) / LX (luxmeter) / HLTA | ||
| LOAD CELL INPUT: | - Input range: -20mV...+20mV (4mV/V) | |
| - s/w limit cells E.S. range: 0.8mV...3.3mV/V | ||
| - Resolutions (Field over the entire scale 2mV/V): 16384 points | ||
| - Converter temperature stability (-10°C...+55°C): 1 point | ||
| - Load cells power supply (max 4 cells 350Ohm): 5V -/+ 2% | ||
| - Fied reading in common way: 1.5V...3.5V | ||
| OUTPUT: | - Until 5 relays 4 AMP-AC1 | (Mechanical endurance 20 millions operations) (Electrical endurance 0.3 millions operations) |
| + 2 relays (optional HPAL) | ||
| + 0-10V (optional HISO) | ||
| DIALOGUE: | - Until 4 Display H=20mm | |
| - 8 + 3 Status lamps | ||
| - 5 Tactile keys (Endurance 3 millions operations) | ||
| COMMUNICATION: | Asynchronous serial TTL full duplex 2400 BAUD / RS485 half duplex 9600 BAUD | |
| - Printer (PR24) | ||
| - RS232C (HRSS) | ||
| - RS485 insulated (HBOX) | ||
| PERIPHERAL: | Synchronous serial 4 wires (SPI) 1MHz | |
| INTELLIGENCE: | HC11 Freescale / 16F Microchip | |
| ROM until 12 Kbytes Nonvolatile | ||
| RAM until 1/2 Kbytes Volatile | ||
| EEPROM until 1/2 Kbytes Pseudo nonvolatile | ||
| Clock 2 MHz (0.5 uSec CPU cycle) | ||
| Data integrity -40....+85 °C | ||
| USING: | Panel mounting dim.: 96x96x58mm | Weight: 370g |
| Wall mounting dim. (/W): 98x125x75mm | Weight: 660g | |
| Power supply: 230Vac (+10%/-15%) 50-60Hz (other voltages on request: 115Vac, 24Vac, 24Vdc, 12Vdc) | ||
| Power consuption typical: 4W | ||
| Operatibility: -10°C....+55°C | ||
| Keyboard waterproof: IP54 | ||
| EMC: | EN 50081-1 (1992)(Emission) EN 50082-2 (1995)(Immunity) | |
|
Fully compliance with European directive 89/336/EEC for electromagnetc compatibility in hard industry and residential environment. |
||
| LVD: | EN / IEC 61010-1 (low voltage) :Safety electric standards concerning low-voltage-directive 73/23/EEC and successes are largerly reached | |